Size the earthing conductor, main protective bonding and supplementary bonding conductors to BS 7671:2018+A2:2022 Chapter 54.
Table 54.7 selection or the Reg 543.1.3 adiabatic method for the earthing conductor; Table 54.8 (PME) or the half-earthing rule for main bonding.

Supply
PME main bonding sizes from the supply neutral (Table 54.8); TN-S / TT from the earthing conductor
mm²
Copper-equivalent csa. Confirm with the DNO
Earthing conductor
mm²
Keys Table 54.7: S ≤ 16 → S; 16 < S ≤ 35 → 16; S > 35 → S/2
A
Earth-fault current at the origin, from the fault-loop study
s
Device operating time at that current. Valid ≤ 5 s
Selects the BS 7671 k table (54.2 separate vs 54.3 incorporated)
Supplementary bonding
mm²
The smaller CPC when connecting two exposed-conductive-parts
Enter the line conductor and CPC csa to size the conductors
Earthing conductor per Table 54.7 (S ≤ 16 → S; 16 < S ≤ 35 → 16; S > 35 → S/2) or the Reg 543.1.3 adiabatic equation S = √(I²t)/k (k from Tables 54.2/54.3); PME supplies additionally floor the earthing conductor at the Reg 544.1.1 main-bonding size (Reg 542.3.1). Main protective bonding per Reg 544.1.1 (≥ half the earthing conductor, ≥ 6, ≤ 25 mm² copper) or Table 54.8 for PME. Supplementary bonding per Reg 544.2 (full/half CPC conductance, 2.5 / 4 mm² minimums). Raw requirements round up to the next standard conductor size.
Copper conductor sizing only: for design guidance only, always verify with a qualified engineer.

About this earthing & bonding conductor sizing calculator

This free earthing and bonding conductor sizing calculator sizes the three protective conductors an installation needs, the earthing conductor, main protective bonding and supplementary bonding, to BS 7671:2018+A2:2022 Chapter 54. It is aimed at UK electricians, electrical designers and inspectors selecting conductor cross-sectional areas at design or verification stage, handling both TN-C-S/PME and TN-S/TT supplies. Everything runs in your browser. Nothing is uploaded.

How the conductor sizes are calculated

The earthing conductor is sized by Table 54.7 selection (S ≤ 16 → S; 16 < S ≤ 35 → 16 mm²; S > 35 → S/2) or the Reg 543.1.3 adiabatic equation S = √(I²t) ÷ k, with k read from Tables 54.2/54.3 for the chosen material, insulation and installation condition; under PME it is additionally floored at the Reg 544.1.1 main-bonding size (Reg 542.3.1). Main protective bonding is Reg 544.1.1 (≥ half the earthing conductor, ≥ 6 and ≤ 25 mm² copper) or Table 54.8 keyed to the supply neutral for PME. Supplementary bonding follows Reg 544.2 (full or half CPC conductance, with 2.5 / 4 mm² minimums). Every raw requirement rounds up to the next standard conductor size.

Reviewed by
Managing Director at Ensign Software. Over 20 years working with UK mechanical, electrical, MEP, ductwork and insulation contractors.
Each calculator cites the standard it follows. For design guidance only: always verify the result with a qualified engineer.

Frequently asked questions

What changes between PME and TN-S/TT supplies?

On a TN-C-S / PME supply the main bonding is sized from the copper-equivalent supply neutral via Table 54.8, and the earthing conductor is floored to that size (Reg 542.3.1). On TN-S or TT the main bonding uses the Reg 544.1.1 half-earthing rule instead. Confirm the neutral size with the DNO.

When is the adiabatic method valid?

The Reg 543.1.3 adiabatic equation assumes all fault energy heats the conductor, which holds for disconnection times of 5 seconds or less. Above 5 s the calculator flags the result as indicative only. Use a non-adiabatic method for slow faults.

Does it size aluminium conductors?

The k values include aluminium for the adiabatic step, but the standard-size ladder and bonding outputs are presented as copper-conductor sizing. Always verify the final selection against BS 7671, the DNO's conditions and the project specification.