Home » Free Calculators » Electrical Voltage Drop Calculator

Check voltage drop using the mV/A/m method.
Enter cable data from manufacturer tables or BS 7671 appendix.

System
V
%
Cable
A
m
mV/A/m
From manufacturer data or BS 7671 tables
Single-phase (2-core) values; auto-scaled ×0.866 when 3φ. Verify against actual cable data.
Enter current, length, and mV/A/m to calculate
Calculations per BS 7671 Appendix 4 (mV/A/m method): dV = mV/A/m × Ib × L ÷ 1000. Single mV/A/m scalar assumed; for cables ≥25 mm² consider separate r/x components.
For design guidance only. Always verify with a qualified engineer.

About this voltage drop calculator

This free voltage drop calculator checks whether a cable run keeps the volt drop within the limit allowed by BS 7671. It is aimed at UK building-services engineers, electrical designers and contractors who need a quick check on a circuit during design or verification. You enter the system type (single-phase or three-phase), supply voltage, design current, one-way cable length and the cable’s mV/A/m figure, and it returns the drop in volts, the drop as a percentage of the supply voltage, and a clear PASS or FAIL against your chosen limit.

How the voltage drop is calculated

The tool uses the mV/A/m method from BS 7671 Appendix 4. The drop is found as dV = mV/A/m × Ib × L ÷ 1000, where Ib is the design current and L is the one-way length. That voltage is then expressed as a percentage of the supply voltage and compared with the maximum allowable drop, 3 % (typical lighting), 5 % (typical other circuits) or a custom value. A single mV/A/m scalar is assumed; the abridged cable presets give the single-phase (two-core) figure and are automatically scaled by √3/2 (≈0.866) when three-phase is selected. The result is indicative design guidance. Always verify against manufacturer data and a qualified engineer.

Reviewed by
Managing Director at Ensign Software. Over 20 years working with UK mechanical, electrical, MEP, ductwork and insulation contractors.
Each calculator cites the standard it follows. For design guidance only: always verify the result with a qualified engineer.

Frequently asked questions

Where do I get the mV/A/m value?

From the cable manufacturer’s data or the BS 7671 tables. You can also pick one of the built-in presets (T&E and SWA copper from 1.5 mm² upwards), which fills the mV/A/m field for you. Verify the figure against the actual cable being used.

What length should I enter?

Enter the one-way length of the cable run. The mV/A/m method already accounts for the return path, so you do not double the length.

What limit should I use, 3 % or 5 %?

The calculator offers 3 % (typical for lighting), 5 % (typical for other circuits) or a custom percentage. Choose the limit appropriate to the circuit and project specification; the result passes when the calculated drop is at or below it.

See Ensign in action

Book a free demo and find out how Ensign can save your business time and money.

By completing this form, you are opting in to receive marketing emails from us. You can unsubscribe at any time.