Add a terminal design/measured flow schedule to identify the index (least-favoured) terminal, each terminal's ratio-to-index target flow, and a suggested work order: CIBSE Commissioning Code A / BSRIA BG49 proportional method.
A commissioning aid, not an automated control system, re-run after each round of damper adjustment with fresh readings.

Terminal schedule
No terminals added yet
Add at least one terminal (design + measured flow) to calculate the balance
Index terminal = lowest %-of-design (measured ÷ design × 100); every other terminal's target = design flow × (index %-of-design ÷ 100). Trim toward this so it matches the index, never trim the index up. Suggested work order = ascending %-of-design (CIBSE Commissioning Code A: "begin at the extremities and work back to the fan"). Tolerance bands (±10% individual terminal, ±5% system total) are a cross-industry commissioning convention (ASHRAE/TAB-spec, corroborated against CIBSE's sister water code), not a single quoted CIBSE Code A figure, advisory only.
For design guidance only. Always verify with a qualified engineer.

About this proportional balancing aid calculator

This free proportional balancing aid calculator supports the proportional method of balancing an air or water distribution system: enter a schedule of design and measured flows for each terminal, and it identifies the index (least-favoured) terminal, gives each terminal a ratio-to-index target flow, and suggests a work order. It is aimed at commissioning engineers and M&E contractors balancing diffusers, radiators or fan-coil branches to the CIBSE Commissioning Code A / BSRIA BG 49 proportional approach. It is a commissioning aid, not an automated control system, re-run it after each round of damper or valve adjustment with fresh readings. Everything runs in your browser. Nothing is uploaded.

How proportional balancing is calculated

Each terminal’s %-of-design = (measured ÷ design) × 100. The index terminal is the one with the lowest %-of-design, the least favoured, which is never trimmed. Every other terminal’s target flow = design × (index %-of-design ÷ 100), so you trim each one down toward the index rather than opening the index up, and the trim needed = measured − target. The suggested work order is ascending %-of-design, following Code A’s principle of starting at the extremities and working back toward the fan or pump. Advisory tolerance bands of ±10% per terminal and ±5% on the system total are a cross-industry convention (ASHRAE / TAB specifications), applied with a tiny epsilon so exact boundary values are forgiven.

Reviewed by
Managing Director at Ensign Software. Over 20 years working with UK mechanical, electrical, MEP, ductwork and insulation contractors.
Each calculator cites the standard it follows. For design guidance only: always verify the result with a qualified engineer.

Frequently asked questions

What is the index terminal?

The index terminal is the one running furthest below its design flow, the lowest %-of-design in the schedule. And it is the reference the rest are balanced against. Because it is already the least favoured, you never trim it up; you close down the others until each matches the same proportion of design, then increase the fan or pump to lift the whole system to duty.

Are the ±10% and ±5% tolerances from CIBSE?

Not directly. CIBSE Commissioning Code A’s own tolerance table is cumulative and scales with outlet count rather than being a single flat figure, so the calculator uses the widely quoted cross-industry bands, ±10% per terminal or branch and ±5% on the main total, as in ASHRAE / TAB specifications, as an advisory check only.

Do I re-run it as I balance?

Yes. The proportional method is iterative: adjust the dampers or valves, take a fresh set of measured flows, and re-enter them. The index terminal and targets can shift as you go, so the tool is a live aid you re-run each round. It does not replace on-site judgement or a commissioning specialist.