Home » Free Calculators » Underfloor Heating Loop Sizing Calculator

Sizes underfloor heating pipe spacing and loop lengths. Add one zone per room; picks the widest (most economical) spacing that meets the target output, checks the BS EN 1264 floor surface-temperature limit, and splits large zones into parallel loops.
Tender-stage sizing check. Always verify against the emitter manufacturer's own output data.

Dwelling
°C
Sourced table domain 35–45°C
m
Pressure-drop budget, 16mm pipe (typical 100m)
Zones
No zones added yet
Add at least one zone to size loops
Pipe spacing and floor surface temperature from BS EN1264 output tables (16mm PE-RT pipe, 75mm screed reference construction. UK Underfloor Heating Ltd, web-verified 2026-07-03), spacings 100/150/200/300mm, mean water temp 35–45°C, room design temp 18–24°C, interpolated between table anchors. Floor surface-temperature limits (occupied 29°C, periphery 35°C, bathroom 33°C) and the 100m/16mm loop-length convention per BS EN 1264-2 and manufacturer installation guides (JG Speedfit, Uponor).
Reference construction only: pipe diameter, screed depth and manifold hydraulic balancing are not parameterised. For design guidance only. Always verify with a qualified engineer.

About this underfloor heating loop sizing calculator

This free underfloor heating loop sizing calculator sizes wet underfloor heating room by room. Add one zone per room and it picks the widest, most economical pipe spacing that meets the target output, checks the BS EN 1264 floor surface-temperature limit for the zone type, and splits large zones into parallel loops within a pressure-drop budget. It is aimed at heating designers and installers laying out manifolds and loop lengths at tender stage across occupied areas, window strips and wet rooms. Everything runs in your browser. Nothing is uploaded.

How the loop sizing is calculated

Output and floor surface temperature come from BS EN 1264 output tables (16 mm PE-RT pipe, 75 mm screed reference construction) at spacings of 100/150/200/300 mm, bilinearly interpolated over the design mean water temperature (35–45 °C) and room design temperature (18–24 °C). The calculator walks the spacings widest-first and keeps the first that meets your target W/m², then checks the resulting surface temperature against the zone limit (occupied 29 °C, periphery 35 °C, bathroom 33 °C). Loop length is coverage = area ÷ (spacing ÷ 1000), split into ceil(coverage ÷ usable length) parallel loops, with a tail allowance of 2 × the manifold distance added per loop to give the total pipe length.

Reviewed by
Managing Director at Ensign Software. Over 20 years working with UK mechanical, electrical, MEP, ductwork and insulation contractors.
Each calculator cites the standard it follows. For design guidance only: always verify the result with a qualified engineer.

Frequently asked questions

Why does the floor covering matter so much?

The covering’s thermal resistance sits between the pipe and the room, so a carpet or thick timber floor passes far less heat than tile or stone at the same water temperature and spacing. The calculator holds a separate BS EN 1264 output table for tile/stone, wood/laminate, carpet and deep-pile/thick wood, so the achievable W/m² reflects the covering you choose.

What is the floor surface-temperature limit?

BS EN 1264 caps the floor surface temperature for comfort and safety: about 29 °C in occupied areas, up to 35 °C in peripheral window strips, and 33 °C in bathrooms and wet areas. The tool reports the surface temperature at the chosen spacing and flags a zone that would breach its limit, often a cue to widen the spacing or lower the water temperature.

Why does it split a zone into several loops?

A single loop has a practical length cap (typically 100 m of 16 mm pipe) set by its pressure drop, so a large zone must run as several parallel loops off the manifold. The calculator divides the pipe coverage by the usable loop length and rounds up, adding a flow-and-return tail for the manifold run. It uses a reference construction only. Verify against the manufacturer’s own output data and a qualified engineer.