Sizes a domestic hot-water cylinder by occupancy: recommended stored litres, the next standard cylinder size, and the heat-source recovery duty for your chosen reheat period.
Tender-stage only. Verify final design to project spec and CIBSE Guide G.
For design guidance only. Always verify with a qualified engineer.
About this DHW storage sizing calculator
This free DHW (domestic hot water) storage sizing calculator sizes a hot water cylinder by occupancy, returning the recommended stored volume, the next standard cylinder size and the heat-source recovery duty for your chosen reheat period. It is aimed at UK plumbing, heating and building-services engineers sizing cylinders and heat sources for dwellings, hotels, offices and schools at tender stage, using the CIBSE Guide G-lineage occupancy tables. Everything runs in your browser. Nothing is uploaded.
How DHW storage and recovery duty are calculated
Storage volume is occupancy × litres-per-occupant from the CIBSE Guide G-lineage table: 45 L per dwelling occupant, 45 L per hotel bedroom, 23 L per boarding-school pupil, and so on. The recovery (reheat) duty comes from sensible heat: ΔT = stored − cold-feed temperature, mass m = volume × 1 kg/L, and energy Q = m · cp · ΔT with cp = 4.186 kJ/kg·K, converted to kWh (÷3600). The heat-source rating is (Q ÷ recovery period) ÷ efficiency. The recommended cylinder is the next standard UK stocked size at or above the storage volume.
Frequently asked questions
Why is the stored temperature 60 °C by default?
60 °C is the usual design store temperature for Legionella control. The cold-feed default of 10 °C is a typical UK design value, giving a 50 K temperature rise. Both are editable if your project specifies otherwise.
What recovery period should I use?
CIBSE Guide G design practice is roughly 1–2 hours. A shorter recovery period reheats the cylinder faster but needs a larger heat source; the calculator shows the recovery duty in kW so you can trade the two off.
What if the volume exceeds the largest cylinder?
Beyond the largest standard size the calculator flags that multiple cylinders or specialist plant are required. The recovery duty figure is still meaningful for sizing the heat source. Verify the final design to project spec and CIBSE Guide G.
Related calculators
- Expansion Vessel Sizing
Free expansion vessel sizing calculator for sealed heating systems - accounts for water volume, temperature range, glycol mix and static height. - Foul Drainage Stack & Branch Sizing Calculator
Sizes discharge stacks & branches to BS EN 12056-2 System III by discharge units: Qww = K√(ΣDU). - Gas Pipe Sizing Calculator
Sizes low-pressure natural gas & LPG pipework by pressure drop to BS 6891:2015 Annex A, segment by segment. - Gas Rate Calculator
Convert a timed meter dial test to heat input in kW and check it against the appliance rating per Gas Safe TB141. - Glycol / Antifreeze Properties Calculator
Find the freeze point, density, specific-heat, viscosity, flow and pressure-drop factors (ASHRAE EG/PG data).